DU144 Automatic Bypass Valve
|
The DU144 automatic bypass valve controls water flow in the heating circuit according to the water pressure across it and is used to maintain a minimum flow rate through the boiler and to limit ciruclation pressure when other water paths are closed. |
A bypass circuit must be installed if the boiler manufacturer requires one, or specifies that a minumum flow rate has to be maintained whilst the boiler is firing. |
|
Materials |
• |
Valve housing, fittings, bonnet and handwheel made of brass |
• |
Spindle made of stainless steel |
• |
Plug made of plastic |
• |
All sealings made of EPDM |
• |
Protection cap made of red plastic |
|
Medium type |
water or water-glycol mixture according to VDI 2035 |
Media temp. |
2 ... 130 oC |
Max. operating pressure |
10 bar |
Differential pressure setpoint range |
0.1 ... 0.6 bar |
Kvs value |
2.3 |
Product description |
with compression fittings for 22mm copper pipe |
Type |
DU144A1001 |