XE-70 thermostat, 230Vac, heatpump & air-conditioner control, T6376/T6377

XE-70 thermostat, 230Vac, heatpump & air-conditioner control, T6376/T6377
Wall mounted line voltage HVAC thermostat.
For control of the fan, compressor, reversing valve, and auxiliary heater in split units, heatpumps, and small air conditioners.
Approvals CE
Protection class IP30
Switch function/capacity SPDT 230Vac, 4 A resistive, 2 A inductive ratings
Terminal max. wire size 1.5 mm2
Temp. setpoint range 10 ... 30 oC
Differential fixed 1 oC
Temperature element vapour filled
Temp. element place built in
Heating /Cooling application H + C
Product literature language Multilingual
Earthing double insulated
Housing (HxWxD) 130 mm | 85 mm | 40 mm 
Additional description T6376B, T6377B1003, T6377B1011 are suitable for heatpumps with reversing valve. T6376B, T6377B1045, T6377B1151 are suitable for air-conditioners.
Heat anticipatorTemperature controlled outputAdditional outputManual operation functionsFan switchFan cycled or continuousHeat/Cool manual modeType
fan + compressor + heaterrev. valveauto/cont.bothH/off/CT6376B1004  PDF
compressorrev. valveon/off switch1/2/3continuousH/fan/CT6377B1003  PDF
fan + compressorrev. valve1/2/3+auto/cont.bothH/off/CT6377B1011  PDF
fan + compressor + heater1/2/3+auto/cont.bothH/off/CT6377B1045  PDF
fan + valve + heateron/off switch1/2/3bothH/em.heat/CT6377B1151  PDF
Accessories
DescriptionAdditional Product Type
Range stops, to limit setpoint adjustment (20 pieces)F42006646-001
Opaque tamperproof cover to prevent thermostat from damageF42008489-001
Transparent tamperproof cover to prevent thermostat from damageF42008489-002
Załączniki
No. Document type (Language) File name File size
1. Karta katalogowa PDF t6376-77-k-pl01r1204.pdf 294 KB